Buckling length is not the storey height.

By Lukas Novák,

Buckling length is not the storey height.

For a column, Lcr depends on how the ends are held: pinned at both ends gives Lcr = L, fixed at both ends with no sway gives 0.5 L, fixed at the base and free at the top gives 2.0 L.

In a sway frame the factor goes above 1.0 and can pass 2.0, which is why the sway classification in EN 1993-1-1 5.2.1 comes before any member check. #eurocode3 #buckling

Replies

Tomás Silva:

The theoretical 0.5 L for a fixed-fixed column almost never exists in a real frame, because the beams that hold the ends are flexible too.

Hannah Moore (reply):

Which is why the distribution factors are worth doing properly. A rotational restraint coefficient of 0.1 at each end is not the same as fixed.