PFC 230×90×32 is an PFC section from the UK Blue Book (SCI P363); MC 9X23.9 is the closest equivalent in the American AISC Shapes Database. MC 9X23.9 carries more bending: 368.71 cm³ of plastic modulus against 355 cm³, 3.7% more. PFC 230×90×32 is the lighter of the two at 32.2 kg/m against 35.6 kg/m, a saving of 9.6% on steel weight. Both are about 229 mm deep, so either fits the same construction zone.

Section properties side by side. Bold marks the more favourable value where one is.
PropertyPFC 230×90×32
PFC
MC 9X23.9
MC
Difference
Mass32.2 kg/m35.6 kg/m-9.6%
Depth230 mm228.6 mm+0.6%
Width90 mm87.6 mm+2.7%
Web thickness7.5 mm10.2 mm-26.5%
Flange thickness14 mm14 mmsame
Area41 cm²45.3 cm²-9.5%
Second moment, major (Iy)3,520 cm⁴3,534 cm⁴-0.4%
Plastic modulus, major (Wpl,y)355 cm³368.71 cm³-3.7%
Elastic modulus, major (Wel,y)306 cm³309.72 cm³-1.2%
Second moment, minor (Iz)334 cm⁴297.2 cm⁴+12.4%
Plastic modulus, minor (Wpl,z)98.9 cm³90.293 cm³+9.5%
Radius of gyration, minor (iz)2.86 cm2.57 cm+11.3%
Torsion constant (It)19.3 cm⁴24.93 cm⁴-22.6%

PFC 230×90×32 to BS EN 1993-1-1:2005 / BS 4-1:2005; MC 9X23.9 to AISC Shapes Database v16.0. Difference is expressed relative to MC 9X23.9.

How to choose between them

On stiffness, MC 9X23.9 has the larger second moment of area: 3,534 cm⁴ against 3,520 cm⁴, a difference of 0.4%. This matters more often than the strength comparison, because on normal floor spans deflection rather than bending capacity sets the beam size - so if the two are close on modulus but apart on inertia, the stiffer one is usually the better answer even when it is not the stronger one.

Measured as bending capacity per kilogram of steel, PFC 230×90×32 is the more efficient section: 11.0 against 10.4 cm³ per kg/m, 6.4% better. Over a floor of repeated beams that difference is real tonnage, though it is often outweighed by whichever section the fabricator can actually source.

The two diverge much more about the minor axis: PFC 230×90×32 has 98.9 cm³ of minor-axis plastic modulus against 90.293 cm³, 9.5% more. If the member sees any minor-axis bending, or if it is unrestrained over a long length and lateral-torsional buckling governs, that gap decides the comparison even though the major-axis numbers looked equivalent.

These come from different catalogues, so treat the swap as a design change rather than a like-for-like substitution. PFC sections are specified to BS EN 1993-1-1:2005 / BS 4-1:2005 and MC to AISC Shapes Database v16.0; the steel grades, tolerances and available lengths differ, connection details and bolt gauges are set out differently, and the two are rarely both stocked in the same market. Check availability before changing a section on a drawing to save 9.6% weight.

In short, MC 9X23.9 is the stronger section and PFC 230×90×32 is the lighter one; where those are the same section, it is the clear choice, and where they are not, decide on whether your design is governed by capacity or by tonnage.

Common questions

MC 9X23.9 is the stronger of the two in bending, with a plastic modulus of 368.71 cm³ against 355 cm³ - 3.7% more. At the same steel grade that translates directly into moment capacity, since M_pl,Rd = W_pl x f_y / gamma_M0.

PFC 230×90×32 at 32.2 kg/m, against 35.6 kg/m for the other - a saving of 9.6%. Over a repeated floor beam that is a real cost difference, but check it against the deflection case before taking it.

Structurally it is the closest equivalent we hold: MC 9X23.9 gives 368.71 cm³ of plastic modulus and 3,534 cm⁴ of inertia against 355 cm³ and 3,520 cm⁴. But they are from different catalogues (BS EN 1993-1-1:2005 / BS 4-1:2005 and AISC Shapes Database v16.0), so this is a design change, not a drop-in swap: re-check deflection, connection detailing and local availability.

MC 9X23.9, with a second moment of area of 3,534 cm⁴ against 3,520 cm⁴ (0.4% more). Deflection under a uniform load goes as 5wL⁴/384EI, so it is inversely proportional to I - on a span where the deflection limit governs rather than strength, this is the number that decides the section.