Compute wind actions to EN 1991-1-4 (Eurocode 1, Part 1-4): basic and peak velocity pressure, terrain category, and external pressure coefficients for walls, roofs, canopies and signboards.
Free online calculator with step-by-step working and one-click Excel (.xlsx) and PDF export.
This wind load calculator works to Eurocode EN 1991-1-4. It takes the basic wind velocity for your site and returns the peak velocity pressure q_p at the reference height, then applies the external and internal pressure coefficients to give the design wind pressure on each zone of the building - walls, flat and pitched roofs, monopitch and duopitch, canopies.
The output is a pressure per zone rather than a single number, because Eurocode wind loading is zonal by construction: the suction at a windward corner is several times the pressure on the middle of a wall, and it is the corner that governs the fixings.
The basic wind velocity is the one input you cannot derive from the geometry: it comes from the wind map in your country National Annex, and it already includes the directional and seasonal factors unless you set them separately.
Take the tool defaults: a basic wind velocity of 27 m/s, terrain category II, reference height 6 m, flat ground and standard air density. Category II has a roughness length z0 = 0.05 m, which is also the reference roughness, so the terrain factor comes out at exactly 0.19.
The exposure factor of 2.04 is worth noting: turbulence and gusting roughly double the pressure relative to the mean wind speed. That factor is where most of the wind load comes from, and it is why using a mean-velocity pressure directly would under-design the structure by half.
Note also that the mean velocity at 6 m is 24.6 m/s, below the 27 m/s basic value - the basic velocity is defined at 10 m, and the wind is slower nearer the ground.
Eurocode divides each wall and roof into zones, and the zone widths come from a single geometric parameter e = min(b, 2h), where b is the crosswind width and h the height. Everything else follows from it: on a wall, zone A is the first e/5 from the windward corner, zone B runs to e, and zone C covers the remainder.
With the default 20 m by 10 m building at 5 m high, e = min(20, 10) = 10 m, so zone A is only 2 m wide and zone B is 8 m. That narrow zone A carries the highest suction on the whole building, which is why cladding fixings are specified at closer centres near corners than in the middle of a facade.
Internal pressure coefficient c_pi acts on the inside face and combines with the external coefficient, so the net pressure on a cladding panel is (c_pe - c_pi) q_p. The tool defaults to the standard envelope of -0.3 and +0.2, which is what EN 1991-1-4 permits when the opening distribution is not known.
The two values must be checked as separate load cases, not averaged. For a roof already in suction, the +0.2 internal pressure adds to the uplift and governs the fixings; for a wall in pressure, the -0.3 case governs. A building with a dominant opening - a large door that could be open in a storm - falls outside the default envelope entirely and needs c_pi calculated from the opening areas.
The peak velocity pressure expression assumes the recommended k_I = 1.0 and the standard logarithmic profile. National Annexes vary these - the UK Annex in particular uses a different procedure with its own terrain and altitude treatment - so check your Annex before using the recommended-value output for a UK project.
The structural factor c_s c_d is taken as 1.0 unless you set it. That is valid for the great majority of buildings under 15 m and for framed buildings under 100 m with normal stiffness, but a slender or dynamically sensitive structure - a tower, a chimney, a long-span roof - needs c_s c_d evaluated properly, and vortex shedding and aeroelastic instability are outside this tool entirely.
Pressure coefficients are for the standard building forms in EN 1991-1-4 Section 7. An unusual geometry, a building with a dominant opening, or a site with significant funnelling between adjacent buildings falls outside the tabulated cases and needs judgement or wind-tunnel data.