CivilAxisCivilAxis
☕ Support🌐 Community

UB 457×191×161 - Section Properties

The UB 457×191×161 is a universal beam with a mass of 161.4 kg/m, an overall depth of 492 mm and width of 199.4 mm. It has a cross-sectional area of 206 cm², a second moment of area Iᵧ of 79800 cm⁴, a plastic modulus Wₚₗ,ᵧ of 3780 cm³, tabulated by CivilAxis from BS EN 10365:2017 (SCI P363 Blue Book).

Mass
161.4 kg/m
Depth
492 mm
Width
199.4 mm
Area
206 cm²
Ask about capacity, buckling or detailing for UB 457×191×161.
🔍 Open the full Steel Catalogue📖 Design theory📐 Worked example
or pick a unit on any row
UB section profile showing the dimension symbols used for UB 457×191×161

Dimension symbols for UB sections. Not to scale.

UB 457×191×161 section properties to BS EN 10365:2017.

Geometry

Depth of sectionh492
Width of sectionb199.4
Web thicknesstw18
Flange thicknesstf32
Root fillet radiusr10.2
Depth between filletsd407.6

Mass and area

Mass per metremass161.4
Cross-sectional areaA206

Bending about the major axis (y-y)

Area moment of inertia about y-axisIy79800
Elastic section modulus about y-axisWel,y3240
Plastic section modulus about y-axisWpl,y3780
Radius of gyration about y-axisiy19.7

Bending about the minor axis (z-z)

Area moment of inertia about z-axisIz4250
Elastic section modulus about z-axisWel,z426
Plastic section modulus about z-axisWpl,z672
Radius of gyration about z-axisiz4.55

Torsion and warping

Torsion constant (St Venant)It515
Warping constantIw2.25

Classification and stability

Flange local-buckling ratiocf/tf2.52
Web local-buckling ratiocw/tw22.6
Buckling parameteru0.881
Torsional indexX16.5

Detailing dimensions

End clearanceC11
Notch dimension NN102
Notch dimension nn44

Surface area

Surface area per metreSA/m1.73
Surface area per tonneSA/t10.7m²/t

Is UB 457×191×161 strong enough?

Simply supported beam, uniform load, major-axis bending - to EN 1993-1-1.

Passes - 59% utilised, deflection governs
Bending29%
393.8 / 1341.9 kNm
Shear8%
157.5 / 1858.4 kN
Deflection59%
16.3 / 27.8 mm

Class 1 section. ULS uses γQ = 1.5 on the load you enter; deflection uses the unfactored load against L/360. Lateral-torsional buckling is not included - the compression flange is assumed restrained.

Common questions about UB 457×191×161

UB 457×191×161 has a mass of 161.4 kg/m, tabulated to BS EN 10365:2017. A 12 m length therefore weighs about 1937 kg, which is the figure to use for a steel take-off or when checking a lift.

UB 457×191×161 has a depth of 492 mm, a width of 199.4 mm, a web thickness of 18 mm, a flange thickness of 32 mm, with a cross-sectional area of 206 cm². These are the nominal dimensions from BS EN 10365:2017; rolling tolerances apply to the delivered section.

The plastic section modulus about the major axis, Wpl,y, is 3,780 cm³, and the elastic modulus Wel,y is 3,240 cm³. Wpl,y is what sets the moment capacity of a Class 1 or 2 section: M_pl,Rd = Wpl,y x f_y / gamma_M0, so at S355 with gamma_M0 = 1.0 this section reaches about 1342 kNm before any stability check.

The second moment of area about the major axis, Iy, is 79,800 cm⁴, and about the minor axis Iz is 4,250 cm⁴. Iy is the value deflection depends on - for a simply supported beam under a uniform load, the midspan deflection is 5wL⁴/384EIy - so on spans where a deflection limit governs rather than strength, this is the number that decides the section.

Its local-buckling ratios are cf/tf = 2.52 for the flange and cw/tw = 22.6 for the web. EN 1993-1-1 Table 5.2 compares these against limits scaled by epsilon = sqrt(235/f_y), so the class depends on the steel grade as well as the geometry - the same section can be Class 1 in S275 and Class 3 in S355. Use the Capacity tab on this page for the classification at a specific grade.

iy is 19.7 cm about the major axis and iz is 4.55 cm about the minor axis. Column buckling is governed by the SMALLER value: the slenderness is lambda = L_cr / i, so with iz = 4.55 cm a 0.5 m effective length already gives lambda = 100. Minor-axis buckling almost always controls unless the weak axis is restrained.

The St Venant torsion constant It is 515 cm⁴, and the warping constant Iw is 2.25 dm⁶. Open sections carry torsion mainly by warping rather than uniform torsion, which is why Iw appears in the lateral-torsional buckling resistance - both values feed M_b,Rd.

Related UB sizes

UB 533×210×82UB 533×165×85UB 533×165×75UB 533×165×66UB 457×191×133UB 457×191×106UB 457×191×98UB 457×191×89

Compare with other sections

Side-by-side properties against the closest equivalent in each catalogue.

vs HE 500 Avs W 18X106vs H-500x300x13x21

Learn more

📘 How to read a steel section table (UB, UC, IPE, HE)📘 Section modulus explained: elastic (Wel) vs plastic (Wpl)📘 IPE vs HE (HEA/HEB): choosing a European steel beam
All UB sizes
Universal Beams (UB)
Full steel section tables
Every UB, UC, hollow, channel & angle section
Open the interactive tool
Search, compare & run EC3 capacity checks
Rate this
No ratings yet
Sign in to join the discussion.