Concrete Cover to Eurocode 2: cmin, Δcdev and cnom
The cover shown on a drawing is the nominal cover, built from a bond minimum, a durability minimum and a construction tolerance. This article explains each term, the structural class system behind the durability values, and works the cover for an internal beam step by step.
What this check does
Cover is the distance from the concrete surface to the nearest surface of reinforcement, including links and stirrups. It protects the steel from corrosion, lets the bars develop bond, and protects them in a fire. The value on the drawing is the nominal cover:
where:
- nominal cover, the value specified on drawings (mm)
- minimum cover (mm)
- allowance in design for deviation during construction (mm)
The minimum cover
The minimum cover is the largest of three requirements:
where:
- minimum cover for bond: the bar diameter for separated bars, plus 5 mm when the maximum aggregate size exceeds 32 mm (mm)
- minimum cover for environmental conditions, from Table 4.4N (mm)
- additive safety element, recommended 0 (mm)
- reduction for stainless steel, recommended 0 (mm)
- reduction for additional protection such as coating, recommended 0 (mm)
The bond term applies to each bar on its own diameter. That is why the link, which sits outside the main bars, often ends up controlled by the main bar requirement.
Structural class and the durability value
Table 4.4N sets by exposure class and structural class. The recommended structural class for a 50-year design life is S4. Table 4.3N moves it up or down: add 2 classes for a 100-year life; subtract 1 when the concrete strength is at least the class listed for that exposure (for example C30/37 in XC1); subtract 1 for slab geometry; subtract 1 with special quality control of concrete production. The class never goes below S1.
Durability values for structural class S4
Exposure | (mm) |
|---|---|
X0 | 10 |
XC1 | 15 |
XC2, XC3 | 25 |
XC4 | 30 |
XD1, XS1 | 35 |
XD2, XS2 | 40 |
XD3, XS3 | 45 |
The construction allowance
The recommended value of is 10 mm. EN 1992-1-1 §4.4.1.3 allows a reduction to between 5 and 10 mm where fabrication is under a quality assurance system that includes measuring the cover, and to between 0 and 10 mm where a very accurate measuring device is used and non-conforming members are rejected. Check the values in your National Annex.
Surfaces cast against the ground
For concrete cast against prepared ground, including blinding, the recommended minimum nominal cover is 40 mm. For concrete cast directly against soil it is 75 mm.
Fire can govern
Cover for fire resistance is set by the axis distance in EN 1992-1-2. For columns, beams and slabs with long fire periods, that requirement is often larger than the durability value, so check both and use the larger.
Worked example
Member: internal beam in a heated building, exposure XC1, 50-year life, structural class S4. Main bars 25 mm, links 10 mm, maximum aggregate 20 mm.
The links are the outermost steel, so the cover is specified to them. Their own requirements:
The main bars need at least their own diameter, and they sit one link diameter further in:
Both conditions give 15 mm to the links. Adding the allowance:
Result: specify 25 mm nominal cover to the links, which gives 35 mm to the main bars. If a 90-minute fire resistance were required, the axis distance from EN 1992-1-2 would be checked next and could increase it.
Key points
, with mm unless quality control justifies less.
is the largest of the bond, durability and 10 mm requirements.
The bond requirement of the main bars often governs the cover to the links.
Structural class S4 is the starting point for a 50-year life; Table 4.3N adjusts it.
Check fire and ground-contact requirements separately.
References
- EN 1992-1-1:2004 - Design of concrete structures - Part 1-1 - §4.4.1 Concrete cover
- EN 1992-1-1:2004 - Table 4.3N and Table 4.4N - structural class and minimum cover for durability